404912-UIM-B-0209
Johnson Controls Unitary Products 11
TABLE 9:
Electrical Data - 3 Ø - 208/230-3-60
1
Models F*FP
Heater
2
Model
Max. Static
& Min. CFM
Total Heat
KW Staging
3
KW MBH W1 Only W2 Only W1 + W2
Static Tap 208 230 208 230 208 230 208 230 208 230
024
2HK06501025B 0.5 Low 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
030
2HK06501025B 0.5 Low 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 High 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
036
2HK06501025B 0.5 Low 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 High 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
040
2HK06501025B 0.5 Low 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 High 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
042
2HK06501025B 0.5 Low 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 Low 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
045
2HK06501025B 0.5 Med 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 High 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
048
2HK06501025B 0.5 Med Low 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 Med Low 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
060
2HK06501025B 0.5 Med 7.5 10.0 25.6 34.1 3.8 5.0 7.5 5.0 7.5 10.0
2HK06501525B 0.5 Med 11.3 15.0 38.6 51.2 3.8 5.0 7.5 10.0 11.3 15.0
1. Heat amps shown at 240V represents maximum heater rating.
2. Heaters are 3 Phase.
3. If first stage heat or 66 is connected to W1, otherwise refer to this table.
TABLE 10:
Electrical Data - (For
Single Source
Power Supply) - Copper Wire 3 Ø - 208/230-3-60
1
Models F*FP
Heater
2
Model
Field Wiring
Min. Circuit Ampacity
Max. O.C.P.
3
Amps/Type
75°C Wire Size - AWG
208V 230V 208V 230V 208V 230V
024
2HK06501025B 41.2 46.5 45 50 8 8
030
2HK06501025B 42.2 47.4 45 50 8 8
2HK06501525B 42.2 47.4 45 50 8 8
036
2HK06501025B 43.1 48.2 45 50 8 8
2HK06501525B 43.1 48.2 45 50 8 8
040
2HK06501025B 42.2 47.4 45 50 8 8
2HK06501525B 42.2 47.4 45 50 8 8
042
2HK06501025B 44.2 49.1 45 50 8 8
2HK06501525B 44.2 49.1 45 50 8 8
045
2HK06501025B 42.8 47.9 45 50 8 8
2HK06501525B 42.8 47.9 45 50 8 8
048
2HK06501025B 48.3 53.9 50 60 8 6
2HK06501525B 48.3 53.9 50 60 8 6
060
2HK06501025B 48.3 53.9 50 60 8 6
2HK06501525B 48.3 53.9 50 60 8 6
1. Heat amps shown at 240V represents maximum heater rating.
2. Heaters are 3 Phase.
3. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.